Makes Excessive Noise - Remote
Fan blade vibrates
Blade is bent Replace fan blade
Fan motor mount is broken Replace motor mount
Compressor vibrates Mounting bolts loose Tighten bolts
Water pump vibrates Pump bearings worn Replace pump
Panels vibrate Mounting screws loose Tighten screws
Test Mode Sequence - Remote
Test Time (seconds) On Off
0 WIV - 30 seconds WP, HGV, Comp, BV, PV
30 WP - 10 seconds WIV, HGV, Comp, BV, PV
40
WP, PV, HGV - 10
seconds
WIV, Comp, BV
50 HGV, Comp - 5 seconds WIV, WP, BV, PV
55 Comp - 15 seconds WIV, HGV, BV, WP, PV
70 None - 5 seconds All
75 HGV - 5 seconds WIV, WP, Comp, BV, PV
80 BV - 5 seconds WIV, HGV, WP, Comp, PV
85 None All – Test Complete
September 2006 Page 56
Problem Likely Cause Probable Solution